Part Number: F2070 | Manufacturer: Westinghouse Electric Corp | NSN: 5925-00-681-6089 (5925006816089) | |
Item Name : Circuit Breaker | CAGE Code: 79500 | FSC: 5925 Circuit Breakers | |
2976 | 05-10-2024 |
We are pleased to inform you that part number F2070 is currently in stock. To receive a quote, please fill out the form below with all necessary information. This part number F2070, with NSN 5925006816089, is manufactured by Westinghouse Electric Corp. We will respond to your quote request within just 15 minutes.
“*” Symbols for mandatory fields
An experienced and dedicated sale representative will contact you within 15 minutes with a quote. For any other questions related to Part F2070, or to expedite your response, please feel free to call us at +1 (714) 705-4780, or email your Bill of Materials (BOM) to sales@veritableaviation.com. We are here to help 24/7, 365 days a year.
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-00-681-6089 Item Description: Circuit Breaker | 5925 | 006816089 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | U | |||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
F2070 | 5 | 2 | 5 |
MRC | Criteria | Characteristic |
---|---|---|
AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
ADAQ | BODY LENGTH | 9.370 INCHES MINIMUM AND 9.380 INCHES MAXIMUM |
ADAT | BODY WIDTH | 4.120 INCHES MINIMUM AND 4.130 INCHES MAXIMUM |
ADAU | BODY HEIGHT | 3.807 INCHES MINIMUM AND 3.817 INCHES MAXIMUM |
ADTV | CASE MATERIAL | PLASTIC |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 7.245 INCHES MINIMUM AND 7.255 INCHES MAXIMUM |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.369 INCHES MINIMUM AND 1.369 INCHES MAXIMUM |
AEBV | UNTHREADED MOUNTING HOLE DIAMETER | 0.276 INCHES MINIMUM AND 0.286 INCHES MAXIMUM |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 4.495 INCHES MINIMUM AND 4.505 INCHES MAXIMUM |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.369 INCHES MINIMUM AND 1.379 INCHES MAXIMUM |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
AJEC | BOSS HEIGHT | 0.120 INCHES MINIMUM AND 0.130 INCHES MAXIMUM |
AKPX | POLE QUANTITY | 2 |
APNQ | ARC QUENCHING METHOD | DEION |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 2 UNTHREADED HOLE |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 70.0 AMPERES AC ALL LOCATIONS AND 70.0 AMPERES DC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 600.0 AC ALL LOCATIONS AND 250.0 DC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 15000.0 AC ALL LOCATIONS AND 10000.0 DC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRP | ULTIMATE TRIP TIME PER POLE IN SECONDS | 400.000 NOMINAL ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | GENERAL PURPOSE |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 40.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
TTQY | TERMINAL TYPE AND QUANTITY | 6 COMPRESSION |
Don’t forget That We Can Respond to Your Instant RFQ Within Fifteen Minutes. Simply Fill Out the Fields On This Website’S Front Page and Click “Request for Quote” and Our Account Managers Will Answer ASAP!